Lewis K. Redmond of Plainfield, Illinois, asks:"We have an Adler/Barbour cold machine refrigerator, which is air-cooled with a small vertical evaporator. The ground wire and its retaining screw on the PCB board somehow were burned black. The technician’s guess was that something must have been thrown across the terminals to have caused this burnout. What measures would you
Author:
Updated:
Original:

Lewis K. Redmond of Plainfield, Illinois, asks:

"We have an Adler/Barbour cold machine refrigerator, which is air-cooled with a small vertical evaporator. The ground wire and its retaining screw on the PCB board somehow were burned black. The technician’s guess was that something must have been thrown across the terminals to have caused this burnout. What measures would you suggest to prevent this from happening again?

Any other ideas on what might have caused this ground wire and retaining screw to be burned black? The 15-amp circuit breaker on AC panel at the dock never tripped. I’m fairly sure this did not occur while sailing, but rather at the dock. Would an ELCI/RCBO device have prevented this short and damage?"

Nigel Calder replies:

Michael Adler, the founder of Adler Barbour, tells me there have been too many changes over the years in basic compressor design and operating systems, plus many changes in the control electronics designs and functions, to give a definitive answer as to what went wrong. However, the problem could have been caused by an internally shorted compressor winding. Michael suspects the external electronics are also fried.

He suggests: A) checking the entire electrical harness with reference to the manual and schematic originally supplied; B) measuring the pin-to-pin compressor resistances per the manual’s trouble-shooting section to see if the compressor has failed; and C) replacing the electronic component, usually called the “module.”

An ELCI likely would not have prevented this damage. An ELCI measures small imbalances in the incoming hot and neutral lines, and trips the circuit if these occur. If it is the compressor that has failed, there will be no imbalance in the AC feed to the electronic module that runs the compressor, as the problem is on “the other side” of this module.

Related

IMG_0207

Ask Sail: How Far to Ease Out?

Q: When sailing dead downwind (assume 22 knots of wind), if the main is eased out to 90 degrees relative to the wind (perpendicular to the wind) are roughly the same forces applied to the sail as to the sail if it isn’t quite out all the way, say, 75 degrees to the wind? My ...read more

200803

Video: A Close Look at the AC75

The AC75 rule crafted for the upcoming 36th America’s Cup was intended to be open to multiple interpretations, and the result has been four very different designs. Coupled with the fact the AC75 is unlike any other boat that has ever come before, the current Cup cycle is fast ...read more

TSP-FB-DEI

US Sailing Invites Public to Diversity Panel

On Tuesday, August 4, US Sailing’s Leadership Forum is hosting a town hall style conversation to help individuals and organizations achieve diversity, equity and inclusion goals. The conversation will be centered on providing practical guidance for conducting outreach and best ...read more

LarryPardey

Eight Bells: Larry Pardey

Canadian-born mariner and author Larry Pardey will be remembered by his friends and fans as a generous spirit who inspired thousands of readers to become sailors and sailors to become adventurers. Whether building his own boats, circumnavigating twice sans engine or stretching ...read more

The-Sailing-Museum-Floorplan

New Sailing Museum Announces Exhibits

The Sailing Hall of Fame-America’s Cup Hall of Fame joint venture to bring a new sailing museum to Newport is moving ahead full steam. Fittingly but unsurprisingly, they’ve announced the name “The Sailing Museum” for the institution to be housed in the historic Armory building. ...read more